Home About us Products Global exports Contact us
 
 
 
Heat Shrinkable
 
 
Heat Shrinkable Medium Voltage Breakouts

(Heat Shrink Non-Tracking Medium Voltage Cable Breakouts)

 
Product Data Sheet
 
Characteristics
 
This data sheet covers the requirements for heat shrink medium voltage breakouts whose dimension will shrink to a predetermined size upon the application of heat above 125 deg. C. Color of the MV breakouts is reddish brown. The MV breakouts are electrically insulating, anti-tracking, UV resistant, weather proof and flame retardant. MV breakouts have three fingers. The main body is internally coated with mastic and covered with a release paper.
 
Typical Applications
The cable breakouts provide insulation and sealing over the crutch of multi-core cables. The mastic sealant provides a water tight environmental seal to the cable. The MV cable breakouts are normally used as an integral part of 3-core cable terminations up to 36 kV.
The following application table gives the MV breakout dimensions.

Breakout
Model
 Breakout main diameter  Finger Diameter Full Length Finger Length
R (mm)
S (mm)
R (mm)
S (mm)
R (mm)
R (mm)
IXL 310
22.00
60.00
8.00
24.00
185.00
45.00
IXL 320
33.00
80.00
16.00
36.00
210.00
50.00
IXL 330
47.00
110.00
20.00
48.00
225.00
75.00
IXL 335
47.00
125.00
20.00
55.00
250.00
75.00
IXL 340
54.00
140.00
27.00
62.00
240.00
65.00
S: As Supplied       R: Fully Recovered

Engineering Drawings


Medium Voltage Breakouts
 
Materials
 
The base material of the MV breakouts is thermally stabilized, cross linked blend of polyolefin and a compatible grade of synthetic rubber. The basic resin is mixed with chemical additives offering resistance against tracking - erosion, fire, oxidation, ozone and other environmental effects. The sealant is butyl rubber based mastic which is electrical insulating, water -proof and anti-tracking.
 
Part Numbering System



Specification Sheet
 
Printing on the Product
 
Each Ikebana breakout is printed with a heat resistant printing ink of white color. Printed information includes: 1. Ikebana logo 2. Product code (either of breakout or of the termination)
 
Packaging
 
MV breakouts are packed individually in a polythene bag. A specified number of MV breakouts are packed inside a standard corrugated carton. The outer carton carries an IKEBANA label with information of the contents and the customer's name. Please refer to the packing information for the numbers.
 
 
Copyright © 2007, Ikebana Engineering Ltd. All Rights Reserved
Best viewed in 800 x 600 resolution.